GB 15322.2-2003 Combustible gas detectors Part 2: Independent combustible gas detectors with a measurement range of 0?100%LEL

time: 2024-08-06 10:47:48
  • GB 15322.2-2003
  • in force

Basic Information

standard classification number

  • Standard ICS number:

    Environmental protection, health and safety>>Fire protection>>13.220.20 Fire protection
  • China Standard Classification Number:

    Medicine, Health, Labor Protection>>Firefighting>>C84 Firefighting Equipment and Supplies

associated standards

  • alternative situation:

    Part of GB 15322-1994
  • Procurement status:

    EN 50054-1999 NEQ%EN 50055-1999 NEQ%EN 50056-1999 NEQ%EN 50057-1999 NEQ%EN 50058-1999 NEQ

Publication information

  • publishing house:

    China Standards Press
  • ISBN:

    155066.1-19550
  • Publication date:

    2003-12-01

Other Information

  • Release date:

    1994-12-22
  • Review date:

    2004-10-14
  • Drafter:

    Wang Yuxiang, Kang Weidong, Ding Hongjun, Fei Chunxiang, Li Keting, Zhao Yingran, Jiang Bo
  • Drafting Organization:

    Shenyang Fire Science Research Institute of Ministry of Public Security
  • Focal point Organization:

    National Fire Protection Standardization Technical Committee
  • Publishing Department:

    General Administration of Quality Supervision, Inspection and Quarantine of the People's Republic of China
  • Competent Authority:

    Ministry of Public Security
Introduction to standardsDescription (Translated English) / download

Skip to download

Summary:

This part specifies the definition, classification, technical requirements, test methods, marking, inspection rules and instructions for use of independent flammable gas detectors. This part applies to independent flammable gas detectors installed and used in general industrial and civil buildings. GB 15322.2-2003 Combustible gas detectors Part 2: Independent flammable gas detectors with a measurement range of 0?100%LEL GB15322.2-2003 standard download decompression password: www.bzxz.net
Standard contentStandard content

Some standard content:

This part of the technical requirements, test methods, inspection rules and instructions for use are mandatory. GB152 effective combustible gas detectors are divided into seven parts: Part 1: Point-type combustible gas detectors with a basic specification of 10E-10E Part 2: Direct-type combustible gas detectors with a standard of 0.1U~0.1E Part 3: Combustible gas detectors with a standard of 0.1U~0.1.FI Part 1: Point-type combustible gas detectors for measuring artificial gas Part 5: Independent combustible gas detectors for measuring artificial gas Part 6: Direct-type gas detectors for measuring artificial gas Part 7: Direct-type gas detectors for measuring artificial gas Part 8: Continuation of combustible gas detectors
15322.22003
This part is Part 2 of GH15322. In the process of sample ordering, the production team formulated the technical requirements of this part according to the national standard G[315322-1394 Technical requirements for combustible gas exchange detectors and the implementation status of the test method in my country in 2015. The technical requirements of this part were formulated according to the national standard [EN50054.KV50055, EN50056ENCC57E50038 (1SSS version) and the national standard, and carried out corresponding test and verification work.
The appendix of this part is the recommended appendix
This part is issued by the Ministry of Public Security of the People's Republic of China and this part is issued by the Sixth Technical Committee of Fire Protection Standardization of the National Fire Protection Standardization Technical Committee. The responsible units of this part are: Hangzhou Fire Science Research Institute of Public Security, and the participating drafting units of this part are: Beijing Keliheng Safety Equipment Co., Ltd., Beijing Anbo Technology Development Co., Ltd., Zhuoyang Huaxin Electric Instrument Co., Ltd., and Shenzhen Te'an Electronics Co., Ltd. The main drafters of this part are Gong Wuxiang, Kang Weidong, Ding Hongxu, Fei Xiang, Xue Duiting and Zhao Leibian. The previous versions of these standards are as follows: GR 15322—1991.
1 Scope
Combustible gas detector
Part 2: Independent combustible gas detector with a measurement range of 0 to 100%LEL
GE15322.2—2003
This part of GB15322 specifies the definition, classification, investment requirements, test methods, marking, test procedures and instruction manual of stand-alone combustible gas detectors.
Part is applicable to stand-alone combustible gas detectors (hereinafter referred to as detectors) installed and used in industrial and wind power buildings and other deep-sea detectors with special performance installed in long-range environments, unless special safety requirements are otherwise specified in relevant standards. 2 Normative references
The following documents have become the terms of this Part through the introduction of this Part (122). For documents with a date of application, their subsequent versions (excluding those with different dates) or sub-versions are not applicable to this Part. However, parties that have reached an agreement on amendments based on this Part are encouraged to use the latest versions of these documents. For documents with no date of application, their new versions shall not apply to this Part.
168X—197 Environmental test method for fire-fighting electrical products and "aldehyde and other parameters" 3 Definitions
This Part adopts the following definitions:
Alarm setting value alarming value
Pre-set gas alarm spectral value
Alarm and other parameters akarnvalue
Detector alarm storage time lamp minimum combustible gas value 3. 3
Explosion (I.FrIowexplnsiveImit the low explosive concentration of gas or algae vapor in the air. 4 Classification
4.1 According to the requirements, it is divided into:
》Anti-explosion type;
b: Non-positive explosion type,
4.2 According to the use environment conditions, it is divided into:
a) Indoor type
l) Outdoor type:
GB15322.22003
5 Technical requirements
5.1 5.1.1 When the concentration of the gas in the monitored area reaches the temporary alarm setting value: it should be able to send out an alarm signal, 51.2 Alarm setting value
Detection When there are two set values ​​of low limit and high limit, the low limit alarm setting value is used as the upper limit, and the upper limit alarm setting value should be 50%1H. For detectors with one alarm setting value, the total alarm setting value should be between 1%LEL and 25%LEL.
5.1.3 Alarm action signal
5.1.3.1 The alarm action value detected in all test items in this part shall not be less than 1%LEL: 1.5.1.3.2 The difference between the alarm action value of the detector and the alarm setting value shall not exceed 3%LEL: 5.t.4 Full range indication deviation
For a detector with only the combustible gas concentration display function, the difference between the displayed value and the actual value shall not exceed 5%LEL, 5. 1. 5 Response time
For detectors with the function of indicating the actual value of combustible gas, the required response time (tt) from the indicated value to the actual value should not exceed the specified time. For detectors with more than the function of indicating the concentration of combustible gas, the response time should not exceed 5.16. The detector should meet the following requirements:
5.1.6.1 When the combustible gas concentration in the monitored area reaches the alarm setting value, the detector should send out an audible and visual alarm signal, and then automatically (or manually) return the detector to the normal monitoring state within 3 days in the active air. 5.1.6.2 When the transmission element of the detector is broken or short-circuited, it should send out an audible and visual alarm signal that is clearly distinguishable from the alarm signal. 5.1.6.3 The detector should be equipped with an audible and visual alarm device to detect the user. 5.1.6.4 For detectors with output control kinetic energy, when the selector sends out an alarm signal, the output control function should be activated. 5.1.7 For detectors powered by batteries, when the battery power is low, it should be able to send out a light indication signal that is different from the alarm signal. The battery performance should meet the following requirements.
5.1.7.! The detector shall be operable for 21 hours when the battery is low. After that, the difference between its alarm action value and the alarm setting value shall not exceed 15%LEL. 5.1.2 The battery life of the detector shall be at least 60 days. 5.1.3 The detector shall be placed at a temperature of -25°C for 24 hours, then restored under normal environmental conditions for at least 24 hours, then placed at a current of 55°C for 24 hours, and then placed under normal environmental conditions for at least 24 hours. After the test, the detector shall not have any damage or corrosion, its operation shall be normal, and the difference between its alarm action value and the alarm setting value shall not exceed -3LEL. 5.1.4 (except for inhalation detectors) In Y, 7, three mutually vertical lines, every 5 rotations, the difference between the alarm action value and the alarm setting value shall not exceed 5%LEL.
5.1.10, concentration reduction performance (not applicable to explosion-proof deep-proof devices) during the liquid effect period: the detector shall send a report signal or a fault signal or an obvious indication signal of the gas concentration measurement diagram. After installation, the operator shall meet the following requirements:
) The detector cannot be in the normal monitoring state; h) If the detector can be in the normal monitoring state (can be operated automatically), the difference between the alarm action value of the detector and the alarm setting value shall not exceed 5%EL.
51.11 Alarm recovery
In normal monitoring Under the condition of the environment, for the measured alarm action value of the same detector, the difference between the alarm action value of the detector and the alarm setting value should not exceed +LEL
5.112 High-speed airflow
GE15322.2-2003
Under the condition of airflow velocity of 6n1/5, the difference between the alarm action value of the detector and the alarm setting value should not exceed ±5LEL5.1.13 Medium fluctuation (except for the single detector in the deep water tank, the zero supply voltage of the detector cabinet is ±25% of the supply voltage, and the difference between its alarm action value and the alarm setting value should not exceed ±3%LEL.
5.1.14 Long-term stability
The detection belt should be able to operate continuously for 28 hours under normal environmental conditions. d. During the test period, the detector shall not send out alarm signals or fault signals. After the test, the difference between the alarm action and the alarm setting shall not exceed 25% THI. 5.115 Insulation withstand voltage performance
The insulation resistance between the external lead-out and the output connector of the detector and the shell shall not be less than 13M2 under the required environmental conditions, and shall not be less than 10M2 under the thermal environment. The above-mentioned parts shall also be subjected to an AC positive current withstand voltage test with a rated voltage tolerance rate of 5 (Hz) and an effective value of 1500V (when the sensitive voltage exceeds EV) or an effective low voltage of 1500V (when the sensitive voltage does not exceed EV) for 5 m! During the test, the detector shall not have discharge or breakdown phenomenon, and the detector function shall be normal after the test. 5.1.16 The detector shall be able to withstand the various tests under the electrical disturbance conditions specified in Table 1. During the test, the following requirements shall be met: During the test, the detector shall not send out an alarm signal or an unreliable fault signal. After the test, the difference between the detector's batch or operating value and the alarm setting value shall not exceed 10 6%. Table 1 Test name Circuit field Optical cavity Electric rescue test control Electrolytic cleaning pulse test adjustment Current / (V/) Frequency range / MHz Voltage / V Micro-frequency Test sample AC power supply) tt||(It is connected with the line)
Normal, life
Each:n
Use battery power, and no external force is applied to the test circuit. 5.1.17
Normal working state
Normal monitoring state
Normal monitoring state
Normal monitoring state If the device can withstand the various tests under the climatic and environmental conditions specified in Table 2, it shall meet the following requirements during and after the test period. The detector shall not send out any fault signal. After the test, the detector shall not be damaged or corroded, and its alarm action shall not be less than the set value. t10%rr
Type of age
High equipment test
Marriage experience
Test monitoring thermal efficiency
Duration/
Disc degree/
Period of use/
Test record
Indoor use type
Outdoor use type A
Work section status table
Normal monitoring system
Normal monitoring regulations inspection
GR15322.2·2003
Test service freezing
Constant promotion of heat test
War doctor you lose
Guarantee the degree!
Special effect time
Table 2 (thread)
Test parts
Outdoor use
Status
Normal monitoring status
5.1.18 The detector shall be subjected to the tests shown in Table 3. During and after the tests, the detector shall meet the following requirements: a) During the tests, the detector shall not send out any fundamental signals or malfunctions; after the tests, the detector shall not have any mechanical damage or loose fastening parts. For example, the difference between the alarm value of the detector and the setting value in the book should not exceed %[,FI.
Test type
Disassembly test
Practice test
Gas transmission batch test
Test length
Car model H
Gadi section
New energy number
Each beat I hit the effect
Limited network height and width/mm
Bake-off effect
Test conditions
-- [ist
5 times the measurement is less than 1
1x the measurement is within 1 kz1 lg,bzxz.net
5 the measurement is greater than 1 g)
working state
normal state
the detector is operated for 1 hour in an environment with a volume fraction of 0.1% ether, and then the detector is operated for 10 hours under the environment conditions.
a) Test room: the detector should not send out an alarm signal or a fault signal; after the test: the difference between the simulated action value of the detector and the alarm setting value should not exceed ±5%1.E1. 5.2 Performance of main components
5.2.1 Indicator light
5.2.1.1 The indicator light of the triode should be safe. 5.2.1.2 The bottom is marked with color. Red indicates a work signal, blue indicates a validity signal, and white indicates that the power is working properly: All indicator lights are white. Under the ambient light, the indicator light should be clearly visible at 3m in front of the detector. 5.2.1 3
5.2.2 Relay 5.2.2.1 The contact point should adopt a double contact structure. 5.2.2.2 The detector should be closed. 5.2.2.3 The same point should not control the internal and external circuits of the detector at the same time. 5.2.3 The components should be protected (moisture-proof, anti-vibration, and cold-proof). 5.2.4 Synchronous devices 52.4.1 Under rated working pressure: The load (A weighted) of the device at 1m above the rated working pressure shall not be less than 7K, 5.2.4.2 Under rated working voltage, the device shall be able to produce sound, 5.2.5 The switch shall be strong and durable, and its housing shall be clearly marked. 5.2. The outer shell of the product shall be made of non-combustible material (oxygen index 32). 6 Test method 6.1 Test requirements 6. 1.1 Test procedures are shown in Table 4:
External crown inspection
Main parts inspection including test items
Electrical performance test
No-power storage test
Reporting position test
Direction test
Reporting main recovery test
High return air test
Electrical output fluctuation test
Full standard elastic elimination without chasing tire
Directional test
Sa exhibition port test
Frequency source resistance test
Western voltage test
Radiation application equipment test
Central total product
Central limit change ball decision test
High test
Low security test
Related security heat test
According to dynamic war release
Drop test
Long-term migration mouse
Nine-state dry search test
The test sample is 12! . And before the test, the detector shall be tested. If there is no period in the relevant provisions, the test conditions shall be as follows: 1. Atmospheric temperature: 7. CB1532222003. CB 15322.2--2003. Temperature 15--3℃. 30%RH-70%RH. H coefficient value 110%R1I atmospheric pressure: kFa16kFa. 6.1.4 If there is no explanation in the relevant provisions, the relevant test data shall be 5%. 6.1.5 The detector shall be inspected for appearance before acceptance, and the test shall be carried out in accordance with the following requirements: a) The text, symbols and signs shall be clear and complete: b) There shall be no corrosion, peeling and blistering on the surface, and no obvious damage. e) The surrounding parts are not moved.
6.1.6 Test gas preparation accuracy
The flammable gas concentration used to prepare the test gas should not be less than 5%. The air used to prepare the test gas should be ash-free and fresh air. The humidity of the prepared gas should meet the positive change conditions. The gas error should not exceed ±2% of the alarm setting value. 6.1.7 Calibration of the detector
Before the test, the alarm points of the detector should be calibrated according to the product manual, and the alarm should be checked and verified. No calibration will be performed thereafter. The detector should be calibrated by the technical verification recorder. 6.1. The detector should be preheated for 1 minute or according to the time specified in the product manual before the test. Then, it should be adjusted according to the instructions. After the test starts, it should be zeroed (except for special requirements for individual tests). 6.2 Main Components Sound Test
6.2.1 Main Components of the Detector
6.2.2 Requirements
The performance of the main components of the detector shall meet the requirements of Article 5.2. 6.2.3 Methods
6.2.3.1 Check and record the usage, color identification, visibility and function marking of the indicator lights; 6.2.3.2 Check and record the function marking of each switch button of the detector; 6.2.3.3 Check and verify the dual-mode electrical appliances;
6.2.3.4 Check and record the transformer status.
6.2.3.5 The detector is in the alarm state, and the alarm signal level of the detector is recorded. Then the voltage of the power supply is reduced by % of the rated voltage, and the detector is observed and recorded. 6.2.3.6 Check the shell of the detector and check the oxygen loss of the external combustion material. 6.3 Functional test
6.3.1 Purpose
To test the output of the detector.
632 Requirements
The output of the detector shall comply with the requirements of 5.1.E.
6.3.3 Procedure
6.3.3.1 After the detector is in the monitoring state for 11 seconds, put the detector in the warning state, observe and record the alarm and other conditions of the detector. The detector with output control function shall also check the start-up performance of the output control function. 6.3.3.2 Remove the detector in alarm state from the combustible gas environment: automatically or automatically recover), observe and record the detector's production and light alarm signal. 5.3.3.3 The sensor element of the detector is disconnected or short-circuited, and observe and record the detector's working status. 6.3.3.4 Operate the detector control mechanism, observe the sound and light alarm of the detector, 6.4 Battery performance test 6.4.1 Purpose To test the battery performance of the detector. 6.4.2 Requirements The battery performance of the detector should meet the requirements of 7.1.7. 6.4.3 Methods 6.4.3.1 Check whether the detector has a low battery indication function. CB15322.2—2003
6.4.3.2 Make the detector work continuously until the low base indication is reached, then measure the detector’s action value according to the method in Article 6.3.
Product.4.3.3 Install the battery-powered detector into the battery and make it stand in the normal monitoring state. After 30 days, check the working condition of the detector:
6.5 Storage test without power supply
6.5.1 Purpose
Check the adaptability of the detector to the storage environment.6.5. 2 Requirements
The detector shall meet the requirements of 6.1.3.
6.5.3 Methods
6.5.3.1 Place the detector with all calibrated and adjusted mass and kinetic energy stops in a low temperature test chamber, and cool the temperature in the test chamber to -25℃±2℃ at a cooling rate not greater than 1/min, and maintain 211.6.5.3.2 Take the test piece out of the low temperature test chamber, or restore it to at least 241 under normal indoor environmental conditions.6.5.3.3 Place the detector in a commercial temperature test chamber. , with a rising rate of no less than 1/min, raise the temperature in the test chamber to 2 and maintain it for 1 hour.
6.5.3.4 Take the detector out of the high temperature test device and place it in the normal environment for at least 24 hours.6.5.3.5 After the test is over, store it in normal environment for several hours and measure the alarm action value of the detector according to the method in 6.3. 6.5.4 The test equipment
shall meet the requirements of GR16838-1997 Section 4. 6. Alarm action value test
6. 6.1 Check the accuracy of the detector alarm setting value. 8.6.2 Requirements The detector's general action value shall meet the requirements of 5.1. 6.6.3 Method 6.6.3.1 Install the detector in the test chamber according to the normal working state requirements, turn on the detector and keep it in the monitoring state for 20 minutes. Turn on the reverse blower to restore the air flow in the test chamber to a stable level of 0.6m/+U.2m/, then increase the test gas concentration at a rate not exceeding 1%LEI./min until the detector sends an alarm signal and measure the alarm action value of the detector. 6.6.4 Test equipment The test equipment shall comply with the provisions of Appendix 4 of this part. 6.7 Position test 6.7. 1 Purpose
To examine the influence of the position of the probe on the alarm action. 6.7.2 Requirements
The position performance of the probe shall meet the following requirements: 1.9. 6.7.3 Method
GB 15322. 2—2003
6.7.3.1Install the probe into the test box according to the working requirements, turn on the power, and keep the probe in the positive monitoring state for 20 minutes.
6.7.3.2Start the ventilator. Make the air flow rate stable at 0.%m/s-0.2m/s. Then increase the test gas concentration at a rate not exceeding 1%LEL/min until the probe sends an alarm signal and the alarm action on the depth measuring axis disappears. After that, the test is carried out every 15 rotations. The alarm action value of each direction on the Y and X axes is measured. 7.3.3 Measure the alarm action value of each direction on the Y and X axes respectively. If the external system and internal component structure of the detector on the Y and X axes have no effect on the air flow accuracy, the test of the Y and X axes is not carried out: 6.7.4 Test equipment
The test equipment shall comply with the provisions of Appendix A of this part. 6. Daily alarm resistance test
6. 8.1 The alarm action value of the detector shall be regenerated every day. 6.82 Requirements
The alarm regeneration of the detector shall meet the requirements of Article 5.2.11. 6.8.3 Method
Repeat the test according to the method in Article 6.6.3, and measure the alarm action value of the detector each time: 6.8.4 Test equipment
The test equipment shall comply with the provisions of Appendix A of this part. 5.9 High-speed air flow avoidance test
6.9.1 Purpose
To test the response of the detector to high-speed air flow. 6.9.2 Requirements
The high-speed air flow resistance of the detector shall meet the requirements of 5.13. 6.9.3 Methods
6.9.3.1 Install the test chamber according to the normal working state requirements, connect the power supply, and quickly put the detector into the normal monitoring state for 20min
6.9.3.2 Start the ventilator to set the air flow velocity in the test chamber at Gm/±0.5m/. Increase the air concentration at a rate not greater than 15%1.K1./min until the detector sends out an alarm signal to verify the alarm effectiveness of the detector. 6.9.4 Test equipment
The test equipment shall comply with the provisions of Appendix A of this Part. 6.10 Voltage fluctuation test
a. 10. 1 The purpose is to test the adaptability of the detector to the electric and hydraulic power of the power grid! 6.10.2 Requirements
The performance of the detector shall be tested in accordance with the requirements of 5.1.13. 6.103 Method
Power the detector/adjust it to 85% of the rated working voltage and stabilize it for 2 hours. Measure the alarm value of the detector according to the method in 6.6.3. Then, discharge the combustible gas in the test box, and restore the detector to the normal monitoring state. Adjust the operating pressure to 115 and the rated working pressure, and keep the output stable for 20)1min. Then measure the alarm action value of the detector according to the method in 6.f.3. 6.104 Test equipment
Test equipment virtual load This part requires the following provisions, 6.11 Full-scale indication deviation test
6.11.1 Full-scale indication deviation test of the detector
6.1.2 The full-scale indication deviation of the detector shall meet the requirements of 5, 1, and 4. 6.11.3 Method
6.11.3.1 Connect the detector to the remote power supply and keep it in the normal monitoring state for 20min, G 15322. 2—20Q3
6.11.3.2 Adjust the flow rate of the combustible gas and clean air required for the gas release separately, and prepare the test gas with a heat release rate of 500m:1./min and a concentration of 1U%, 25%, 59%, 75%, and 90% of the detector fullness respectively. After the test, send the test gas to the sensor element of the detector for at least 1W. The indication of the detector in each case is 6.11.4 Test verification
) Gas release instrument!
) Gas release instrument,
6.12 Response time test
6.12.1 Purpose
Check the response time of the detector,
6.12 2 Requirements
When replacing the detector, it should meet the requirements of 5.1. 6.12.3 Method
6.12.3.1 Connect the detector to the TV and make it work normally. Monitor the change of concentration. For the detector with a sensitive concentration display function, adjust the flow rate of the effective gas and clean filling gas entering the gas detector, and prepare a flow rate of m and a concentration of the detector full range. After calibration, input the prepared gas to the sensor of the detector and start the timing device at the same time. When the detector displays the actual value of 9, stop the timing and record the response time of the detector).|| tt||31233For the detection medium without combustible gas display, adjust the combustible gas and clean air flow rate entering the gas conditioner, prepare a test gas with a flow rate of m/min and a pressure of 1. times the alarm action value of the detector, and deliver the prepared test gas to the detection element through the calibration cover: start the timing device at the same time, and when the deep measuring end sends an alarm signal, stop counting and record the average alarm response time of the detector.
6.124 Test equipment
) Gas rate analyzer
623 High concentration condensate test
6.13.1 Purpose
To test the responsiveness of the high concentration filter of the detector. 6.73.2 Requirements
The high concentration condensate performance detected shall meet the requirements of 3.1 and 1. 6.13.3 Fangsong
B.13.3.1 Install the detector in the explosion test sieve, and place it in the normal monitoring state for 20 minutes. 6.13.3.2 Send the volume of 100% flammable gas to the sensor element of the detector through the sieve at a flow rate of 0 cm/min, and keep it for 2 minutes to extract the flammable gas. Then immerse the detector in clean air for 31 rrmil. During the test, observe and record the working state of the detector; after the test, if the detector can be in the monitoring state, measure the alarm action value of the detector according to the force method in Article 3:
6.13.4 Test equipment
Lusen test specification.
B15322.2-2003
6.14 Insulation resistance test
6. 14. 1 Purpose
To inspect the insulation performance of the detector
6.14.2 Requirements
The insulation performance of the detector shall meet the requirements of 5.1.15. 6.14.3 Method
6.14.3.1 Under working conditions, use an insulation resistance test device to apply 400V±5V DC voltage to the following parts of the detector for 60 ℃ and measure their insulation resistance: (1) between the external output terminal and the external charger with insulation requirements; (2) between the power supply terminal and the casing (the power switch is in the parallel position and not connected to the power supply). 6.14.3.2 Place the tester in a drying oven at 4% ± 5% for 96 hours and in a damp heat test chamber at 40°C ± 2°C and relative humidity of 5% to 95% for 96 hours, then place it in a normal environment for 60 hours. Measure the insulation resistance according to the above method:
74.4 Test equipment
Test the absolute resistance according to the technical requirements (it can also be tested with a ohmmeter or a meter): Test range: Ma~500Mn
Small division 0.1M0;
6.15 Withstand voltage test
6.15. 1 Purpose
To test the withstand voltage performance of the detector
6.15.2 Requirements
The withstand voltage performance of the detector shall be in accordance with the requirements of 5.1.15. 6.153 Method
6.15.3.1 After the withstand voltage test, apply an alternating voltage of 5Hz ± 1% (rated medium voltage exceeds 50V) or 50Hz + %300V = 10% (rated voltage does not exceed 50V) to the following positions of the detector at a voltage increase rate of 100V/~590V/, and stand for 695 ± 55 seconds, and observe and record the phenomena that occur during the test. 1) Between the external circuit breaker and the external power supply: b) Between the power supply terminal and the external power supply point: (the power supply is turned off, and the power supply is not turned off according to the power supply). 6.15.3.2 After the test, perform a functional check on the detector according to the provisions of 6.1.1. 6.15.4 Test equipment
The withstand voltage test equipment shall meet the following technical requirements: Test power supply, 10V--1500V, continuously adjustable effective value, lock 50Hz+1%, voltage rise and fall rate 100V/s--50C V's..
Timing: 60±5s.
6.16 Radio-phosphorus field test
6.16.1 Purpose
To test the suitability of the detector to operate in the radiation field environment. 6.16.2 Requirements
The radiation electric field resistance performance of the detector shall meet the requirements of 5.1.16. 6.16.3 Method
6.16.3.1 Place the detector on the insulated table. Turn on the power and keep the detector in the normal monitoring state for 2) min. 1i
Headquarters H15322.2—2003
6.16.3.2 Place the transmitting antenna in the middle according to the test equipment. The detector and the output magnetic field meter are 1m away from the transmitting line. The transmitting antenna is placed in the middle. The detector and the output magnetic field meter are placed 1m away from the transmitting line. The transmitting antenna is placed in the middle. The output magnetic field meter and the output magnetic field meter are placed 1m away from the transmitting line ... In the frequency range of 1MHz--! 000MHz, the test circuits are respectively carried out with horizontal polarization and vertical polarization of the air carrier. 16.3.4 During the test, observe and record the working status of the tester. 16.3.5 The test tube should be carried out in a screen. In order to avoid large measurement errors, the position of the air carrier should meet the requirements of Figure 2. 6.16.3.6 After the test, measure the action value of the tester by S.6.3 and S.6.4 Test equipment The test equipment should meet the requirements of Chapter 4 of R16R3%-1997. 2 Antenna location diagram
6.17 Electrostatic discharge test
6.17.1 Purpose
To test the suitability of the detector to electrostatic discharge caused by static electricity personnel and objects: 6.17.2 Requirements
The anti-static discharge performance of the detector shall meet the requirements of 5.1G. 617 3 Method
6.17.3.1 Place the inductor on the insulator bracket and connect it to the averaging board at a distance of not less than 1W\1. Turn on the power and let the detector dry for 11 seconds.Turn on the power and make the depth detector in the normal state for 2 minutes. 1i
Headquarters H15322.2—2003
6.16.3.2 Place the transmitting antenna in the middle of the test equipment according to 1, and the detector and the output magnetic field measuring instrument are respectively 1m away from the transmitting line. The transmitting antenna is connected to the transmitter. The power of the signal is generated by the transmitter. Figure 1 Layout of the test equipment
6.16.3.3 Adjust the frequency of the signal generated by 1MH2~10VMH$. The reading of the instrument is 15V/m. During the test, the frequency of the signal generated by 1MH2 is constant at a speed of not more than 0.0050ct/min. At the same time, the detector should be rotated to observe and record the working conditions of the detector. If the transmitting antenna used is directional, the transmitting antenna should be reversed first and aimed at the detector for testing. In the frequency range of 1MHz--! 000MHz, the test circuit is carried out with horizontal polarization and vertical polarization of the antenna respectively. 16.3.4 During the test, observe and record the working status of the detector. 16.3.5 The test tube should be carried out in a screen. In order to avoid large measurement errors, the position of the antenna should meet the requirements of Figure 2. 6.16.3.6 After the test, measure the action value of the detector by S.6.3 and S.6.4 Test equipment The test equipment should meet the requirements of Chapter 4 of R16R3%-1997. 2 Antenna location diagram
6.17 Electrostatic discharge test
6.17.1 Purpose
To test the suitability of the detector to electrostatic discharge caused by static electricity personnel and objects: 6.17.2 Requirements
The anti-static discharge performance of the detector shall meet the requirements of 5.1G. 617 3 Method
6.17.3.1 Place the inductor on the insulator bracket and connect it to the averaging board at a distance of not less than 1W\1. Turn on the power and let the detector dry for 11 seconds.Turn on the power and make the depth detector in the normal state for 2 minutes. 1i
Headquarters H15322.2—2003
6.16.3.2 Place the transmitting antenna in the middle of the test equipment according to 1, and the detector and the output magnetic field measuring instrument are respectively 1m away from the transmitting line. The transmitting antenna is connected to the transmitter. The power of the signal is generated by the transmitter. Figure 1 Layout of the test equipment
6.16.3.3 Adjust the frequency of the signal generated by 1MH2~10VMH$. The reading of the instrument is 15V/m. During the test, the frequency of the signal generated by 1MH2 is constant at a speed of not more than 0.0050ct/min. At the same time, the detector should be rotated to observe and record the working conditions of the detector. If the transmitting antenna used is directional, the transmitting antenna should be reversed first and aimed at the detector for testing. In the frequency range of 1MHz--! 000MHz, the test circuit is carried out with horizontal polarization and vertical polarization of the antenna respectively. 16.3.4 During the test, observe and record the working status of the detector. 16.3.5 The test tube should be carried out in a screen. In order to avoid large measurement errors, the position of the antenna should meet the requirements of Figure 2. 6.16.3.6 After the test, measure the action value of the detector by S.6.3 and S.6.4 Test equipment The test equipment should meet the requirements of Chapter 4 of R16R3%-1997. 2 Antenna location diagram
6.17 Electrostatic discharge test
6.17.1 Purpose
To test the suitability of the detector to electrostatic discharge caused by static electricity personnel and objects: 6.17.2 Requirements
The anti-static discharge performance of the detector shall meet the requirements of 5.1G. 617 3 Method
6.17.3.1 Place the inductor on the insulator bracket and connect it to the averaging board at a distance of not less than 1W\1. Turn on the power and let the detector dry for 11 seconds.
Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.
Please remember: "bzxz.net" is the combination of the first letters of the Chinese pinyin of the four Chinese characters "standard download" and the international top-level domain name ".net". ©2024 Standard download websitewww.bzxz.net Mail:[email protected]