
GB 12972.5-1991 Mining rubber-sheathed flexible cables Part 5: Mobile rubber-sheathed flexible cables with rated voltage 0.66/1.14 kV and below
time:
1991-06-06 16:00:00
- GB 12972.5-1991
- Abolished
Standard ID:
GB 12972.5-1991
Standard Name:
Mining rubber-sheathed flexible cables Part 5: Mobile rubber-sheathed flexible cables with rated voltage 0.66/1.14 kV and below
Chinese Name:
矿用橡套软电缆 第5部分:额定电压0. 66/1.14 kV及以下移动橡套软电缆
Standard category:
National Standard (GB)
-
Date of Release:
1991-06-06 -
Date of Implementation:
1992-03-01 -
Date of Expiration:
2009-04-01
Standard ICS number:
Electrical Engineering>>Wires and Cables>>29.060.20 CablesChina Standard Classification Number:
Electrician>>Electrical Materials and General Parts>>K13 Cable and Accessories
alternative situation:
Replaced GB 1170-1974; replaced by GB/T 12972.5-2008
Release date:
1991-06-06Review date:
2004-10-14Drafter:
Liu Fenglin, Tang KaizongDrafting Organization:
Shanghai Cable Research Institute, Fushun Branch of China Coal Research Institute and other unitsFocal point Organization:
National Technical Committee for Standardization of Wires and CablesProposing Organization:
Ministry of Mechanical and Electronic Industry of the People's Republic of ChinaPublishing Department:
State Bureau of Technical SupervisionCompetent Authority:
China Electrical Equipment Industry Association

Skip to download
Summary:
This standard specifies product varieties, technical requirements, test methods and inspection rules for mobile rubber-sheathed flexible cables with rated voltage 0.66/1.14kV. This standard applies to copper core rubber insulated rubber sheathed flexible cables for mobile equipment with a rated voltage of 0.66/1.14kV and below. This standard should be used together with GB l2972.1. GB 12972.5-1991 Rubber-sheathed flexible cables for mining use Part 5: Mobile rubber-sheathed flexible cables with rated voltage 0.66/1.14 kV and below GB12972.5-1991 Standard download and decompression password: www.bzxz.net

Some standard content:
National Standard of the People's Republic of China
Rubber-sheathed flexible cables for mining
Part 5: Mobile rubber-sheathed flexible cables with rated voltage 0.66/1.14kV and below
Flexible rubber-sheathed cables for mining purposesPart5Flexiblecablesforratedvoltageupto0.66/1.14kvSubject content and scope of application
GB12972.5-91
Replaces GB1170-74
This standard specifies the rated voltage 0.66/1.14kV mobile rubber sheathed flexible cable Product varieties, technical requirements, test methods and inspection rules. This standard applies to copper core rubber insulated rubber sheathed flexible cables for mobile equipment with a rated voltage of 0.66/1.14kV and below. This standard should be used together with GB12972.1. 2 Usage characteristics
2.1 Rated voltage U./U are 0.38/0.66 and 0.66/1.14kV respectively. 2.2 The long-term allowable operating temperature of cable conductors is 65°C. 2.3 The minimum bending radius of the cable is 6 times the cable diameter. 2.4 Yellow-sheathed cables must not be exposed to sunlight for a long time. 3 model
cable models are shown in Table 1.
Table 1
UY-0.38/0.66
UYP-0.38/0.66
UYP-0.66/1.14| |tt||Name
Mobile rubber-sheathed flexible cable for mining
Mobile shielded rubber-sheathed flexible cable for mining
Mobile shielded rubber-sheathed flexible cable for mining| |tt||3.2 cable type as shown in Figure 1.
State Bureau of Technical Supervision approved on 1991-06-06
purpose
Rated voltage 0.38/0.66kV power connection for various underground mobile coal mining equipment
rated voltage 0.38/0.66kV Power supply connection for various underground mobile coal mining equipment
Rated voltage 0.66/1.14.kV Power supply connection for various underground mobile coal mining equipment
Implemented on 1992-03-01||tt ||4 specifications
UYP-0.38/0.66
UYP-0.66/1.14
GB12972.5—91
Figure 1
UY-0.38/ 0.66
1—power core conductor; 2 filling; 3—insulation; 4—insulation shield; 5—ground core conductor; 6—outer sheath
Cable specifications should comply with Table 2a and Table 2 2b regulations. Cable specifications should comply with Table 2a and Table 2b. Table 2a
Outer diameter of cable
Number of cores × nominal conductor cross-section, mm2
Power corewww.bzxz.net
Ground core
3×4|| tt||3×6
3×50||tt| |3×70
1 ×16
power core
insulated
nominal thickness
1.4|| tt||1.4
Sheath mark|| tt||Thickness
5.0||tt ||5.0
UY-0.38/0.66
minimum value
Maximum
33.4| |tt||39.8
UYP-0.38/0.66
Minimum||tt| |23.7
Max Value
57.1| |tt||Number of cores × nominal conductor cross-section, mm2
Power wire core
3×25||tt| 3×35
5 technical requirements
ground core
1× 10
GB 12972.5-91
Table 2b
Power wire core
Insulation
Nominal thickness
5.1 The technical requirements of cables should comply with Table 3 and Table 4. 5.2 Single wires in conductors are allowed to be tinned. The surface of the conductor can be covered with an isolation layer. Note: Discoloration or brittleness of the isolation layer after vulcanization will not be assessed. 5.3 Insulation
Sheath mark
Weighing thickness
5.5||tt ||5.5
5.3.1 The insulation of the power wire core should comply with the XJ-00A regulations in GB7594.2. 5.3.2 If the ground core has an insulating coating, it should comply with the XJ-00A regulations in GB7594.2. 5.3.3 The insulation shield adopts the Class A structure in Table 5 of GB12972.1. 5.4 Cable core
5.4.1 The position of the ground core complies with the requirements of GB12972.1 Article 7.4b. 5.4.2 The stranded pitch diameter ratio of the cable core should not be greater than: power wire core cross-section 4~16mm
power wire core cross-section 25~95mm
5.5 sheath
... ....
..·12
5.5.1 If there is a rubber inner sheath, it should not be lower than the XJ-02A requirements in GB7594.6. Cable outer diameter
UYP-0.66/1.14
minimum value
5.5.2 The outer sheath rubber should comply with the XH-03A requirements in GB7594.7, but the tear strength should not be less than 7.5N/mm. Table 3
Nominal cross-section of power wire core
25| |tt||Insulation resistance at 20℃
Mn·km minimum value
120| |tt||Power wire core nominal cross-section
mm||tt| |Maximum
Insulation resistance at 20℃
MQ·km minimum value
80||tt| |6 Testing and Inspection Rules
Products are tested as specified in Table 4.
Serial number
1.6|| tt||2
2.7||tt| |2.8
Project name
Structural dimensions
Conductor
Insulation thickness||tt ||Shielding layer
Cable core
Sheath thickness
Cable outer diameter
Cable performance
Conductor resistance
Insulation resistance|| tt||Transition resistance
Power frequency AC voltage
Burning test
Mechanical impact test
Extrusion test
Insulation physics Mechanical
Performance
Sheath physical machinery
Performance
Identification mark
Delivery length
GB12972.5-91||tt ||Table 4
Technical requirements
GB12972.1 Article 4.1 and this standard Article 5.2 GB12972.1 Article 5.2 and this standard Table 2a and Table 2b this standard Article 5.3.3| |tt||GB12972.1 Article 7 and this standard Article 5.4 GB12972.1 Article 8 and this standard Table 2a and Table 2b this standard Table 2a and Table 2b
GB12972.1 Table 1||tt ||Table 3 of this standard
GB12972.1 Article 11.4
(not applicable to UY-0.38/0.66)
GB12972.1 Table 8
GB12972.1 Article 11.6
16~35mm2*2 times
50~95mm2..3 times
UY-0.38/0.66 and UYP-0.38/0.66***30kNUYP-0.66 /1.1440kN
Article 5.3 of this standard
Article 5.5 of this standard
Article 10 of GB12972.1
Article 11.12 of GB12972.1
Note: St means periodic testing, which should be conducted at least once a year. Additional notes:
This standard is proposed by the Ministry of Mechanical and Electronics Industry of the People's Republic of China. This standard is under the jurisdiction of the Shanghai Cable Research Institute of the Ministry of Mechanical and Electronic Industry. Test type
T,St|| tt||T,St
Test method
GB4909. 2
Visual inspection
Hanging visual inspection
GB3048.4| |tt||GB3048.5
GB12972.1 Appendix D
GB12666.2
GB12972.1 Appendix A
GB12972. 1Appendix B
GB2951
GB2951
GB6995
Meter Counter
This standard was approved by the Shanghai Cable Research Institute of the Ministry of Mechanical and Electronic Industry and the General Administration of Coal Research Fushun Branch of the hospital and other units are responsible for drafting. The main drafters of this standard are Liu Fenglin and Tang Kaizong.
Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.
Rubber-sheathed flexible cables for mining
Part 5: Mobile rubber-sheathed flexible cables with rated voltage 0.66/1.14kV and below
Flexible rubber-sheathed cables for mining purposesPart5Flexiblecablesforratedvoltageupto0.66/1.14kvSubject content and scope of application
GB12972.5-91
Replaces GB1170-74
This standard specifies the rated voltage 0.66/1.14kV mobile rubber sheathed flexible cable Product varieties, technical requirements, test methods and inspection rules. This standard applies to copper core rubber insulated rubber sheathed flexible cables for mobile equipment with a rated voltage of 0.66/1.14kV and below. This standard should be used together with GB12972.1. 2 Usage characteristics
2.1 Rated voltage U./U are 0.38/0.66 and 0.66/1.14kV respectively. 2.2 The long-term allowable operating temperature of cable conductors is 65°C. 2.3 The minimum bending radius of the cable is 6 times the cable diameter. 2.4 Yellow-sheathed cables must not be exposed to sunlight for a long time. 3 model
cable models are shown in Table 1.
Table 1
UY-0.38/0.66
UYP-0.38/0.66
UYP-0.66/1.14| |tt||Name
Mobile rubber-sheathed flexible cable for mining
Mobile shielded rubber-sheathed flexible cable for mining
Mobile shielded rubber-sheathed flexible cable for mining| |tt||3.2 cable type as shown in Figure 1.
State Bureau of Technical Supervision approved on 1991-06-06
purpose
Rated voltage 0.38/0.66kV power connection for various underground mobile coal mining equipment
rated voltage 0.38/0.66kV Power supply connection for various underground mobile coal mining equipment
Rated voltage 0.66/1.14.kV Power supply connection for various underground mobile coal mining equipment
Implemented on 1992-03-01||tt ||4 specifications
UYP-0.38/0.66
UYP-0.66/1.14
GB12972.5—91
Figure 1
UY-0.38/ 0.66
1—power core conductor; 2 filling; 3—insulation; 4—insulation shield; 5—ground core conductor; 6—outer sheath
Cable specifications should comply with Table 2a and Table 2 2b regulations. Cable specifications should comply with Table 2a and Table 2b. Table 2a
Outer diameter of cable
Number of cores × nominal conductor cross-section, mm2
Power corewww.bzxz.net
Ground core
3×4|| tt||3×6
3×50||tt| |3×70
1 ×16
power core
insulated
nominal thickness
1.4|| tt||1.4
Sheath mark|| tt||Thickness
5.0||tt ||5.0
UY-0.38/0.66
minimum value
Maximum
33.4| |tt||39.8
UYP-0.38/0.66
Minimum||tt| |23.7
Max Value
57.1| |tt||Number of cores × nominal conductor cross-section, mm2
Power wire core
3×25||tt| 3×35
5 technical requirements
ground core
1× 10
GB 12972.5-91
Table 2b
Power wire core
Insulation
Nominal thickness
5.1 The technical requirements of cables should comply with Table 3 and Table 4. 5.2 Single wires in conductors are allowed to be tinned. The surface of the conductor can be covered with an isolation layer. Note: Discoloration or brittleness of the isolation layer after vulcanization will not be assessed. 5.3 Insulation
Sheath mark
Weighing thickness
5.5||tt ||5.5
5.3.1 The insulation of the power wire core should comply with the XJ-00A regulations in GB7594.2. 5.3.2 If the ground core has an insulating coating, it should comply with the XJ-00A regulations in GB7594.2. 5.3.3 The insulation shield adopts the Class A structure in Table 5 of GB12972.1. 5.4 Cable core
5.4.1 The position of the ground core complies with the requirements of GB12972.1 Article 7.4b. 5.4.2 The stranded pitch diameter ratio of the cable core should not be greater than: power wire core cross-section 4~16mm
power wire core cross-section 25~95mm
5.5 sheath
... ....
..·12
5.5.1 If there is a rubber inner sheath, it should not be lower than the XJ-02A requirements in GB7594.6. Cable outer diameter
UYP-0.66/1.14
minimum value
5.5.2 The outer sheath rubber should comply with the XH-03A requirements in GB7594.7, but the tear strength should not be less than 7.5N/mm. Table 3
Nominal cross-section of power wire core
25| |tt||Insulation resistance at 20℃
Mn·km minimum value
120| |tt||Power wire core nominal cross-section
mm||tt| |Maximum
Insulation resistance at 20℃
MQ·km minimum value
80||tt| |6 Testing and Inspection Rules
Products are tested as specified in Table 4.
Serial number
1.6|| tt||2
2.7||tt| |2.8
Project name
Structural dimensions
Conductor
Insulation thickness||tt ||Shielding layer
Cable core
Sheath thickness
Cable outer diameter
Cable performance
Conductor resistance
Insulation resistance|| tt||Transition resistance
Power frequency AC voltage
Burning test
Mechanical impact test
Extrusion test
Insulation physics Mechanical
Performance
Sheath physical machinery
Performance
Identification mark
Delivery length
GB12972.5-91||tt ||Table 4
Technical requirements
GB12972.1 Article 4.1 and this standard Article 5.2 GB12972.1 Article 5.2 and this standard Table 2a and Table 2b this standard Article 5.3.3| |tt||GB12972.1 Article 7 and this standard Article 5.4 GB12972.1 Article 8 and this standard Table 2a and Table 2b this standard Table 2a and Table 2b
GB12972.1 Table 1||tt ||Table 3 of this standard
GB12972.1 Article 11.4
(not applicable to UY-0.38/0.66)
GB12972.1 Table 8
GB12972.1 Article 11.6
16~35mm2*2 times
50~95mm2..3 times
UY-0.38/0.66 and UYP-0.38/0.66***30kNUYP-0.66 /1.1440kN
Article 5.3 of this standard
Article 5.5 of this standard
Article 10 of GB12972.1
Article 11.12 of GB12972.1
Note: St means periodic testing, which should be conducted at least once a year. Additional notes:
This standard is proposed by the Ministry of Mechanical and Electronics Industry of the People's Republic of China. This standard is under the jurisdiction of the Shanghai Cable Research Institute of the Ministry of Mechanical and Electronic Industry. Test type
T,St|| tt||T,St
Test method
GB4909. 2
Visual inspection
Hanging visual inspection
GB3048.4| |tt||GB3048.5
GB12972.1 Appendix D
GB12666.2
GB12972.1 Appendix A
GB12972. 1Appendix B
GB2951
GB2951
GB6995
Meter Counter
This standard was approved by the Shanghai Cable Research Institute of the Ministry of Mechanical and Electronic Industry and the General Administration of Coal Research Fushun Branch of the hospital and other units are responsible for drafting. The main drafters of this standard are Liu Fenglin and Tang Kaizong.
Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.
- Recommended standards
- HG/T 2391-1992 Cord Tube Laminating Machine
- GB/T 4110-1983 Pulse Code Modulation Communication System Series
- SJ/T 10587.1-1994 Technical data of Type DW-305 electronic glass
- GB/T 27835-2011 Test method for hazard classification of chemicals—12 m drop test
- GBZ 8-2002 Diagnostic criteria for occupational acute organophosphorus pesticide poisoning
- HG/T 3495-1999 Chemical reagent Eosin
- QB/T 1499-2000 Claw-type twist-off cap
- GB/T 3007-1982 Test method for moisture content of ordinary aluminum silicate refractory fiber felt
- JB/T 6722-1993 Magnetic particle inspection of internal combustion engine connecting rods
- QB/T 2361-1998 惯性玩具通用技术条件
- JB/T 10124-1999 Machine tool fixture parts and component dials
- JB/T 9168.9-1998 General process code for cutting processing - Gear processing
- GB/T 11798.7-2001 Technical requirements for the verification of motor vehicle safety testing equipment Part 7: Technical requirements for the verification of axle (wheel) load meters
- GB/T 15689-1995 Determination of acidity of oil in oilseeds
- GB/T 4574-1984 Test method for actual circuit noise and circuit noise of simulated system load in simulated communication network
Please remember: "bzxz.net" is the combination of the first letters of the Chinese pinyin of the four Chinese characters "standard download" and the international top-level domain name ".net". ©2024 Standard download websitewww.bzxz.net Mail:[email protected]