标准下载网/Chapter 5 - Protective measures for persons

Chapter 5 - Protective measures for persons

电气装置中的人员与设备保护措施

Chapter 5 - Protective measures for persons

Protective Measures for Persons and Installations

版本年份 2000 文件语言 英语 全文 6 页 格式 PDF
Chapter 5 - Protective measures for persons 电气装置中的人员与设备保护措施封面

标准信息

STANDARD INFORMATION
标准编号
Chapter 5 - Protective measures for persons
所属分类
其他国外标准与工程资料
发布机构
DIN/VDE
版本年份
2000
文件语言
英语
文件格式
PDF
文件页数
6 页
文件大小
1.05 MB

中文名称为参考译名,文件语言以原文为准。

· 更新:

标准简介

OVERVIEW

中文简介

该文档详细阐述了低压电气装置(1000V及以下)中针对人员的安全保护措施,包括直接接触防护和间接接触(故障)防护。内容涵盖了依据DIN VDE 0100和VDE 0106标准,通过绝缘、外壳防护、剩余电流保护装置(RCD)及接地系统协调来实现电气安全的具体要求。

English summary

This document details safety protective measures for persons in low-voltage electrical installations (up to 1000 V), covering protection against direct and indirect contact. It outlines requirements based on DIN VDE 0100 and VDE 0106 standards, including insulation, enclosures, residual current devices (RCDs), and earthing system coordination to ensure electrical safety.

以上为根据文件整理的内容简介。

相关标签

标准内容预览

DOCUMENT PREVIEW
点击页码切换内容
Chapter 5 - Protective measures for personsPDF 第 1 页 · 原页码 1

5.1.3 Protection by extra low voltage

Equipment of safety class II and type-tested assemblies with total insulation are identified with the symbol □ as per DIN 40014.

Conductive parts within the enclosure must not be connected to the protective conductor, otherwise it will be a device in safety class I. If protective conductors must be routed through insulated equipment, they must be insulated like live conductors.

Exceptions

Measures for protection in case of indirect contact are not required for the following equipment:

  • lower parts of overhead line insulators (except when they are within reach)
  • steel towers, steel-concrete towers, packing stands
  • equipment that is not likely to come into contact by any part of the human body because of its small dimensions (e.g. 50 mm x 50 mm) or because of its configuration,
  • metal enclosures for protection of equipment of safety class II or equivalent.

As per DIN VDE 0100-410 (VDE 0100 Part 410) the use of the SELV and PELV extra low-voltage systems (Fig. 5-6) can offer protection in case of direct and indirect contact. Extra low voltages in accordance with these specifications are AC voltages ≤ 50 V and DC voltages ≤ 120 V. Corresponding specifications for current circuits with limited discharge energy (≤ 350 m J) are in preparation.

Current sources for supplying extra low-voltage systems of the SELV and PELV types must be safely separated from the infeed system, e.g. as isolating transformer with shielding (DIN EN 60742 (VDE 0551) or as motor generators (DIN VDE 0530), but not as autotransformer, potentiometer and the like.

The SELV extra low voltage, apart from secure separation of the current circuits, requires that neither live parts nor metallic enclosures must be earthed. Protective measures to prevent direct contact, such as barriers, enclosures or insulation are not necessary here if the rated voltage does not exceed AC 25 V and DC 60 V.

Live parts and metallic enclosures may be earthed with the PELV extra low voltage. Protective measures against direct contact are also not necessary here with rated voltages below AC 25 V and DC 60 V, if metallic enclosures, which can be touched simultaneously, and other conductive parts are connected to the same earthing system.

The FELV extra low voltage is supplied by a power source without a safe isolation. Earthing the current circuits is permitted. Metallic enclosures must be connected to the protective conductor on the primary side of the power source. Protection against direct contact and in case of indirect contact is generally required (DIN VDE 0100-470 (VDE 0100 Part 470).

Auxiliary circuits in switchgear installations are often operated with extra low voltage. With reference to protection in case of indirect contact, the systems with safe isolation (SELV, PELV) are to be recommended, particularly with small direct cross sections, because in contrast to the FELV system, no additional measures are required. Consistent safe isolation from the supply network must be assured by the selection of the equipment in the entire current circuit.