标准下载网/Earthing Systems-Basic Constructional Aspects

Earthing Systems-Basic Constructional Aspects

接地与电磁兼容:接地系统 - 基本构造方面

Earthing Systems-Basic Constructional Aspects

Earthing Systems - Basic Constructional Aspects

版本年份 2004 文件语言 英语 全文 6 页 格式 PDF
Earthing Systems-Basic Constructional Aspects 接地与电磁兼容:接地系统 - 基本构造方面封面

标准信息

STANDARD INFORMATION
标准编号
Earthing Systems-Basic Constructional Aspects
所属分类
其他国外标准与工程资料
发布机构
Copper Development Association
版本年份
2004
文件语言
英语
文件格式
PDF
文件页数
6 页
文件大小
427.22 KB

中文名称为参考译名,文件语言以原文为准。

· 更新:

标准简介

OVERVIEW

中文简介

该文档是Leonardo电力质量倡议(LPQI)的一部分,由铜发展协会(CDA)发布。它提供了关于接地系统设计和计算的实用指导,涵盖了接地电阻计算、接地电极材料选择及腐蚀问题。内容还详细阐述了接地系统的功能,包括保护接地、功能接地和防雷接地,并强调了在故障条件下限制接地电位以确保人身安全的基本要求。

English summary

This document, part of the Leonardo Power Quality Initiative (LPQI) and published by the Copper Development Association (CDA), provides practical design guidance for earthing systems. It covers the calculation of earthing resistance, selection of electrode materials, and corrosion considerations. The text also details the functions of earthing systems, including protective, functional, and lightning protection earthing, emphasizing safety requirements regarding touch voltage during fault conditions.

以上为根据文件整理的内容简介。

相关标签

标准内容预览

DOCUMENT PREVIEW
点击页码切换内容
Earthing Systems-Basic Constructional AspectsPDF 第 1 页 · 原页码 1

Earthing Systems - Basic Constructional Aspects

Functions of earthing systems and fundamental requirements

The function of an earthing system is to provide:

  • protective earthing
  • functional earthing in electric power systems
  • lightning protection.

The protective earthing system provides interconnection or bonding of all metallic parts (exposed and extraneous conductive parts) that a person or an animal could touch. Under normal, fault-free, circumstances there is no relative potential on these parts, but under fault conditions a dangerous potential may arise as fault current flows. The function of an earthing system is the protection of life against electric shock, the fundamental requirement being that the earthing potential, VE, at a prospective short circuit current, IE, does not exceed the permissible touch voltage, VF:

VE ≤ VF (1)

Thus, the maximum permitted value of earthing resistance is:

R = VF / IE (2)

where IE is the single-phase short circuit current under the most unfavourable conditions.

In industrial installations, as well as in power substations, earthing systems of the low- and high-voltage systems are often common due to limited ground area available. In isolated earth (IT) type installations, protective earthing should be implemented as a common system with the high-voltage protective earthing, independently of the type of neutral point operation (i.e. insulated or compensated).

Functional earthing relates to the need for certain points of the electrical system to be connected to the earthing system in order to ensure correct operation. A typical example is earthing of the neutral point of a transformer.

Lightning protection earthing conducts lightning currents to the earth. Lightning currents can reach very high peak values, ip, and cause very high values of earthing electrode potentials, VE, which can be calculated with the following formula:

VE ≈ √( (L · dip/dt)² + (ipRp)² ) (3)

where:

L is the inductance of earthing electrode and lightning conductors

Rp is the impulse resistance of the earthing electrode.

Depending on the lightning current and the properties of the earthing system, potential VE can reach very high values, up to some hundreds or even thousands of kV. Because these values are much higher than the network operating voltages, lightning often causes back-flashover or induced over-voltages in the network. Thus, full protection of installations against lightning requires the provision of a system of lightning arrestors and spark gaps.

Resistance and surface potential distribution of typical earth electrode constructions

Simple surface earth electrodes are metal rods, strips or pipes placed horizontally under the surface of the ground at a given depth, t, as shown in Figure 1. Usually the length of these elements, l, is much larger than t. Given this assumption, the earth surface potential distribution of the earth electrode, in direction x perpendicular to the length l, is described by the following formula: