DOCUMENT PREVIEWReferences
Amend 1 Sep 1993
For the purposes of New Zealand Building Code compliance, acceptable reference documents include only the quoted edition and specific amendments as listed below.
|
Amend 2 Feb 1998 Standards New Zealand NZS 5261: 1996 The installation of gas burning appliances and equipment |
Where quoted AS1 1.2.2, 5.0.1, 9.0.1 |
|
Miscellaneous Publication Gas Service Technology Volume 1 – Benn Technical Books |
AS1 1.3.1 |
6
Status of Compliance Documents
Compliance Documents are prepared by the Department of Building and Housing in accordance with section 22 of the Building Act 2004. A Compliance Document is for use in establishing compliance with the New Zealand Building Code.
A person who complies with a Compliance Document will be treated as having complied with the provisions of the Building Code to which the Compliance Document relates. However, a Compliance Document is only one method of complying with the Building Code. There may be alternative ways to comply.
Users should make themselves familiar with the preface to the New Zealand Building Code Handbook, which describes the status of Compliance Documents and explains alternative methods of achieving compliance.
Defined words (italicised in the text) and classified uses are explained in Clauses A1 of the Building Code and in the Definitions at the start of this Compliance Document.
| Date | Alterations | ||
|---|---|---|---|
| First published | July 1992 | ||
| Amendment 1 | September 1993 | p. vi, References | |
| Reprinted incorporating Amendment 1 | October 1994 | ||
| Amendment 2 | 28 February 1998 | pp. i and ii, Document History p. vi, References p. 3, 1.2.2 | p. 4, 5.0.1 p. 5, 9.0.1 |
| Note: Page numbers relate to the document at the time of Amendment and may not match page numbers in current document. | |||
Document Status
The most recent version of this document, as detailed in the Document History, is approved by the Chief Executive of the Department of Building and Housing. It is effective from 28 February 1998 and supersedes all previous versions of this document.
People using this Compliance Document should check for amendments on a regular basis. The Department of Building and Housing may amend any part of any Compliance Document at any time. Up-to-date versions of Compliance Documents are available from www.dbh.govt.nz
2
New Zealand Building Code
Clause G11 Gas as an Energy Source
This Clause is extracted from the New Zealand Building Code contained in the First Schedule of the Building Regulations 1992.
70 Building Regulations 1992 1992/150 FIRST SCHEDULE—continued Clause G11—GAS AS AN ENERGY SOURCE | |
|
Provisions OBJECTIVE G11.1 The objective of this provision is to: (a) Safeguard people from injury arising from the use of gas as an energy source, (b) Safeguard people and other property from the risk of fire or explosion, and (c) Safeguard people from loss of amenity due to the gas supply being inadequate for the intended use. FUNCTIONAL REQUIREMENT G11.2 In buildings where gas is used as an energy source, the supply system shall be safe and adequate for its intended use. PERFORMANCE G11.3.1 Supply systems shall be constructed to maintain a safe pressure range appropriate to the appliances and the type of gas used. G11.3.2 The gas supply to all appliances in a single ventilated space, shall be fitted with an automatic cut-off activated by failure of any continuous forced ventilation system used for combustion, ventilation or safe operation of a fixed gas appliance. G11.3.3 A flued fixed gas appliance shall have no adverse interaction with any other flued appliance. G11.3.4 Supply systems shall have isolation devices which permit the whole installation, or individual items of apparatus, to be isolated from the supply for maintenance, testing, fault detection or repair. |
Limits on application |
3
FIRST SCHEDULE—continued
1992/150 Building Regulations 1992 71
| Provisions | Limits on application |
|---|---|
|
G11.3.5 Where gas is supplied from an external source, the supply system within buildings shall be constructed to avoid the likelihood of: (a) Contamination of the external supply from other gas sources within the building. (b) Adverse effects on the pressure of the external supply; and (c) The external supply pipe acting as an earthing conductor. G11.3.6 The location and installation of meters and service risers shall meet the requirements of the network utility operator. |
4
Contents
| Page | |
|---|---|
| References | 7 |
| Definitions | 9 |
| Verification Method G11/VM1 | 11 |
| Acceptable Solution G11/AS1 | 13 |
| 1.0 Pipe Sizing | 13 |
| 1.1 Pressure ranges | 13 |
| 1.2 Pressures less than 1.5 kPa | 13 |
| 1.3 Pressures above 1.5 kPa | 13 |
| 1.4 Flow velocities | 13 |
| 2.0 Pressure Regulation | 13 |
| 2.1 Regulators | 13 |
| 3.0 Over-pressure Protection | 13 |
| 3.1 Safety devices | 13 |
| 4.0 Pipework Installation | 14 |
| 5.0 Flues | 14 |
| 5.1 Flue materials | 14 |
| 5.2 Safety devices | 14 |
| 5.3 Fire dampers | 14 |
| 6.0 Automatic Extinguishers | 14 |
| 7.0 Protection of Supply | 14 |
| 7.1 Gas contamination | 14 |
| 7.2 Low pressure | 14 |
| 8.0 Gas Meter Location | 15 |
| 9.0 Alternative Solution | 15 |
| Index | 17 |
5
References
Amend 1 Sep 1993
For the purposes of New Zealand Building Code compliance, acceptable reference documents include only the quoted edition and specific amendments as listed below.
|
Amend 2 Feb 1998 Standards New Zealand NZS 5261: 1996 The installation of gas burning appliances and equipment |
Where quoted AS1 1.2.2, 5.0.1, 9.0.1 |
|
Miscellaneous Publication Gas Service Technology Volume 1 – Benn Technical Books |
AS1 1.3.1 |
6