JB/T 6776-1993 Rated power, voltage and speed of industrial frequency gasoline generator sets

time: 2024-07-14 08:22:03
  • JB/T 6776-1993
  • in force

Basic Information

standard classification number

  • China Standard Classification Number:

    Electrical Engineering>>Power Equipment for Power Generation>>K52 Generator Set

associated standards

Publication information

Other Information

  • Focal point Organization:

    Lanzhou Power Vehicle Research Institute
  • Publishing Department:

    Lanzhou Power Vehicle Research Institute
Introduction to standardsDescription (Translated English) / download

Skip to download

Summary:

This standard specifies the rated power, rated voltage and rated speed of industrial frequency gasoline generator sets. This standard applies to units with a frequency of 50Hz and gasoline engines driving AC single-phase and three-phase generators. JB/T 6776-1993 Rated power, voltage and speed of industrial frequency gasoline generator sets JB/T6776-1993 Standard download decompression password: www.bzxz.net
Standard contentStandard content

Some standard content:

Mechanical Industry Standards of the People's Republic of China
Compilation of Electrical Industry Standards (1999 Edition) Generator Sets (Including Mobile Power Stations) Professional Volume
Volume 1
Beijing Institute of Electrical Technology and Economics, Machinery Industry, 2000
Compilation of Electrical Industry Standards (1999 Edition) Generator Sets (Including Mobile Power Stations) Professional Volume, Volume 1
Beijing Institute of Electrical Technology and Economics, Machinery Industry, 2000
Mechanical Industry Standards of the People's Republic of China
Rated Power, Voltage and Speed ​​of Industrial Frequency Gasoline Generator Sets Subject Content and Scope of Application
JB/T6776—1993
This standard specifies the rated power, rated voltage and rated speed of industrial frequency gasoline generator sets (hereinafter referred to as units). This standard applies to units with a frequency of 50Hz and gasoline engines driving AC single-phase and double-phase generators. Reference standards
GB5320
GB8365
Terms and terms for internal combustion engine power stations
General technical conditions for industrial frequency gasoline generator sets shall comply with the provisions of GB5320.
General requirements
This standard is used in conjunction with GB8365. bZxz.net
Rated values
5.1 Recommended rated power; (0.3); 0.5, 0.6#0.751; 1.2, 1.5; 2; 3; 4, 5, 6, 8; 10, 12; 15kW. Note: ①The values ​​in brackets are reserved values,
②The corresponding power factor: single-phase is 0.8 (lagging), or 0.9 (lagging), or 1.0; three-phase is 0.8 (after filling). 5.2 Rated voltage
Single-phase: 230V.
Note: When used as a power source for projecting movies, the rated voltage of a single-phase unit can be 220V. b. Three-phase: 400V.
5.3 Rated speed: 3000/min.
Note: The rated speed of the generator is the rated speed of the unit. 6
Parameter coordination
The recommended coordination of the rated power and rated voltage of the unit is as specified in Table 1. Table 1
Rated voltage
Approved by the Ministry of Machinery Industry on August 21, 1993
(0.3)0.5,0.6;0.75,11.2,1.5,2,34,56234;56#8,10,1215
Implemented on October 1, 1993