
GB 12972.8-1991 Mining rubber sheathed flexible cables Part 8: Mining electric drill cables with rated voltage 0.3/0.5 kv
time:
1991-06-06 16:00:00
- GB 12972.8-1991
- Abolished
Standard ID:
GB 12972.8-1991
Standard Name:
Mining rubber sheathed flexible cables Part 8: Mining electric drill cables with rated voltage 0.3/0.5 kv
Chinese Name:
矿用橡套软电缆 第8部分:额定电压0. 3/0.5 kv矿用电钻电缆
Standard category:
National Standard (GB)
-
Date of Release:
1991-06-06 -
Date of Implementation:
1992-03-01 -
Date of Expiration:
2009-04-01
Standard ICS number:
Electrical Engineering>>Wires and Cables>>29.060.20 CablesChina Standard Classification Number:
Electrician>>Electrical Materials and General Parts>>K13 Cable and Accessories
alternative situation:
Replaced GB 1170-1974; replaced by GB/T 12972.8-2008
Release date:
1991-06-06Review date:
2004-10-14Drafter:
Liu Fenglin, Tang KaizongDrafting Organization:
Shanghai Cable Research Institute, Fushun Branch of China Coal Research Institute and other unitsFocal point Organization:
National Technical Committee for Standardization of Wires and CablesProposing Organization:
Ministry of Mechanical and Electronic Industry of the People's Republic of ChinaPublishing Department:
State Bureau of Technical SupervisionCompetent Authority:
China Electrical Equipment Industry Association

Skip to download
Summary:
This standard specifies product varieties, technical requirements, test methods and inspection rules for mining electric drill cables with rated voltage 0.3/0.5kV. This standard applies to rated voltage 0.3/0.5kV mining copper core rubber insulated rubber sheathed electric drill cables. This standard should be used together with GB 12972.1. GB 12972.8-1991 Mining rubber sheathed flexible cables Part 8: Mining electric drill cables with rated voltage 0.3/0.5 kv GB12972.8-1991 Standard download and decompression password: www.bzxz.net

Some standard content:
National Standard of the People's Republic of China
Mining Rubber Sheathed Flexible Cables
Part 8: Rated Voltage 0.3/0.5kV
Mining Electric Drill Cables
Flexiblerubber-sheathed cablesforminingpurposesPart 8 :Flexibledrill cables forratedvoltageof0.3/0.5kV
1 Subject content and scope of application
GB12972.8-91
Replaces GB1170--74
This standard specifies the rated Product varieties, technical requirements, test methods and inspection rules for mining electric drill cables with voltage of 0.3/0.5kV. This standard applies to rated voltage 0.3/0.5kV mining copper core rubber insulated rubber sheathed electric drill cables. This standard should be used together with GB12972.1. 2Usage characteristicswwW.bzxz.Net
2.1 Rated voltage U/U is 0.3/0.5kV.
2.2 The long-term allowable operating temperature of the cable conductor is 65°C. 2.3 The minimum bending radius of the cable is 6 times the cable diameter. 3 model
3.1 cable model is shown in Table 1.
UZ-0.3/0.5
UZP-0.3/0.5
Mine The electric drill cable
is called
mine shielded electric drill cable
The cable type is shown in Figure 1.
State Bureau of Technical Supervision 1991-06-06 Approved Table 1
Purpose
Power connection for electric drills with rated voltage 0.3/0.5kV and below in coal mines 1992- 03-01Implementation
Specifications
UZ-0.3/0.5
GB 12972.8—91
UZP-0.3/0.5
Figure 1
1 - Power core conductor; 2 - Power core insulation; 3 - Semiconducting shielding layer; 4 - Filling core; 5 - Ground core conductor: 6 - Ground core cladding; 7 1. Sheath; 8. Control core conductor; 9. Control core insulated cable specifications should comply with Table 2.
Number of cores × nominal conductor cross-section, mm2
Power wire core
3×2.5||tt| |3×4
Ground core
5 Technical requirements
Control wire core
Conductor structure
Number/single wire
Nominal diameter
GB12972.8—91
Table 2| |tt||power core
protection
insulation
nominal thickness
The technical requirements of 1.0
5.1 cable shall comply with Table 3 and Table 4. 5.2 Conductor
5.2.1 The single wire in the conductor should be tinned, and the surface of the conductor can be covered with an isolation layer. Note: Discoloration or brittleness of the isolation layer after vulcanization will not be assessed. 5.3 Insulation
Sleeve
Nominal thickness
Cable outer diameter|| tt||UZ-0.3/0.5
minimum value
5.3.1 power core The insulation of the control wire core should comply with the XJ-00A regulations in GB7594.2. 5.3.2 If the ground core has an insulating coating, it should comply with the XJ-00A regulations in GB7594.2. 5.3.3 The insulation shield adopts the Class A structure in Table 5 of GB12972.1. 5.4 Cable core
5.4.1 The position of the control wire core complies with the provisions of Article 7.2c of GB12972.1. 5.4.2 The position of the ground core complies with the requirements of GB12972.1 Article 7.4b. 5.4.3 The stranded pitch diameter ratio of the cable core should not be greater than 5. 5.5 Sheath
5.5.1 The sheath is a single-layer structure, and its performance complies with the XH-03A regulations in GB7594.7. 6 Test and inspection rules
Products are tested according to Table 3 and Table 4.
Table 3
Nominal cross-section of power wire core
Insulation resistance at 20℃||tt| |MO·km minimum value
maximum value
22.6| |tt||mm
UZP-0.3/0.5
maximum value
minimum value
20.9||tt ||22.4
20℃ conductor DC resistance
a/km maximum value
23.6||tt ||23.8
Serial number
2.6| |tt||2.7
Project name
Structural dimensions
Conductor
Insulation thickness
Shielding Layer
Cable core
Sheath thickness
Cable outer diameter
Cable performance
Conductor resistance
Insulation resistance
Transition resistance
power frequency AC voltage
combustion test
insulation physical machinery
performance
sheath physical machinery||tt ||Performance
Identification mark
Delivery length
GB 12972.8-91
Table 4
Technical requirements
Chapter 5.2 of this standard Article and Table 2
GB12972.1 Article 5.2 and this standard Table 2
This standard Article 5.3.3
GB12972.1 Article 7 and this standard GB12972 .1 Article 8 and Table 2 of this standard
Table 2 of this standard
Table 3 of this standard
Table 3 of this standard
Not more than 1kQ (not applicable to UZ -0.3/0.5) GB12972.1 Table 8
GB12972.1 Article 11.6
Article 5.3 of this standard
Article 5.5 of this standard
GB12972.1 Article 10
GB12972.1 Article 11.12
Note: St means periodic testing, which should be conducted at least once a year. Additional notes:
This standard is proposed by the Ministry of Mechanical and Electronics Industry of the People's Republic of China. This standard is under the jurisdiction of the Shanghai Cable Research Institute of the Ministry of Mechanical and Electronic Industry. Test type
T,St|| tt||T,St
Test method
Visual inspection
Visual inspection of twist direction
GB12972.1 Appendix D
GB12666.2 | | tt | Branch hospitals and other units are responsible for drafting. The main drafters of this standard are Liu Fenglin and Tang Kaizong.
Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.
Mining Rubber Sheathed Flexible Cables
Part 8: Rated Voltage 0.3/0.5kV
Mining Electric Drill Cables
Flexiblerubber-sheathed cablesforminingpurposesPart 8 :Flexibledrill cables forratedvoltageof0.3/0.5kV
1 Subject content and scope of application
GB12972.8-91
Replaces GB1170--74
This standard specifies the rated Product varieties, technical requirements, test methods and inspection rules for mining electric drill cables with voltage of 0.3/0.5kV. This standard applies to rated voltage 0.3/0.5kV mining copper core rubber insulated rubber sheathed electric drill cables. This standard should be used together with GB12972.1. 2Usage characteristicswwW.bzxz.Net
2.1 Rated voltage U/U is 0.3/0.5kV.
2.2 The long-term allowable operating temperature of the cable conductor is 65°C. 2.3 The minimum bending radius of the cable is 6 times the cable diameter. 3 model
3.1 cable model is shown in Table 1.
UZ-0.3/0.5
UZP-0.3/0.5
Mine The electric drill cable
is called
mine shielded electric drill cable
The cable type is shown in Figure 1.
State Bureau of Technical Supervision 1991-06-06 Approved Table 1
Purpose
Power connection for electric drills with rated voltage 0.3/0.5kV and below in coal mines 1992- 03-01Implementation
Specifications
UZ-0.3/0.5
GB 12972.8—91
UZP-0.3/0.5
Figure 1
1 - Power core conductor; 2 - Power core insulation; 3 - Semiconducting shielding layer; 4 - Filling core; 5 - Ground core conductor: 6 - Ground core cladding; 7 1. Sheath; 8. Control core conductor; 9. Control core insulated cable specifications should comply with Table 2.
Number of cores × nominal conductor cross-section, mm2
Power wire core
3×2.5||tt| |3×4
Ground core
5 Technical requirements
Control wire core
Conductor structure
Number/single wire
Nominal diameter
GB12972.8—91
Table 2| |tt||power core
protection
insulation
nominal thickness
The technical requirements of 1.0
5.1 cable shall comply with Table 3 and Table 4. 5.2 Conductor
5.2.1 The single wire in the conductor should be tinned, and the surface of the conductor can be covered with an isolation layer. Note: Discoloration or brittleness of the isolation layer after vulcanization will not be assessed. 5.3 Insulation
Sleeve
Nominal thickness
Cable outer diameter|| tt||UZ-0.3/0.5
minimum value
5.3.1 power core The insulation of the control wire core should comply with the XJ-00A regulations in GB7594.2. 5.3.2 If the ground core has an insulating coating, it should comply with the XJ-00A regulations in GB7594.2. 5.3.3 The insulation shield adopts the Class A structure in Table 5 of GB12972.1. 5.4 Cable core
5.4.1 The position of the control wire core complies with the provisions of Article 7.2c of GB12972.1. 5.4.2 The position of the ground core complies with the requirements of GB12972.1 Article 7.4b. 5.4.3 The stranded pitch diameter ratio of the cable core should not be greater than 5. 5.5 Sheath
5.5.1 The sheath is a single-layer structure, and its performance complies with the XH-03A regulations in GB7594.7. 6 Test and inspection rules
Products are tested according to Table 3 and Table 4.
Table 3
Nominal cross-section of power wire core
Insulation resistance at 20℃||tt| |MO·km minimum value
maximum value
22.6| |tt||mm
UZP-0.3/0.5
maximum value
minimum value
20.9||tt ||22.4
20℃ conductor DC resistance
a/km maximum value
23.6||tt ||23.8
Serial number
2.6| |tt||2.7
Project name
Structural dimensions
Conductor
Insulation thickness
Shielding Layer
Cable core
Sheath thickness
Cable outer diameter
Cable performance
Conductor resistance
Insulation resistance
Transition resistance
power frequency AC voltage
combustion test
insulation physical machinery
performance
sheath physical machinery||tt ||Performance
Identification mark
Delivery length
GB 12972.8-91
Table 4
Technical requirements
Chapter 5.2 of this standard Article and Table 2
GB12972.1 Article 5.2 and this standard Table 2
This standard Article 5.3.3
GB12972.1 Article 7 and this standard GB12972 .1 Article 8 and Table 2 of this standard
Table 2 of this standard
Table 3 of this standard
Table 3 of this standard
Not more than 1kQ (not applicable to UZ -0.3/0.5) GB12972.1 Table 8
GB12972.1 Article 11.6
Article 5.3 of this standard
Article 5.5 of this standard
GB12972.1 Article 10
GB12972.1 Article 11.12
Note: St means periodic testing, which should be conducted at least once a year. Additional notes:
This standard is proposed by the Ministry of Mechanical and Electronics Industry of the People's Republic of China. This standard is under the jurisdiction of the Shanghai Cable Research Institute of the Ministry of Mechanical and Electronic Industry. Test type
T,St|| tt||T,St
Test method
Visual inspection
Visual inspection of twist direction
GB12972.1 Appendix D
GB12666.2 | | tt | Branch hospitals and other units are responsible for drafting. The main drafters of this standard are Liu Fenglin and Tang Kaizong.
Tip: This standard content only shows part of the intercepted content of the complete standard. If you need the complete standard, please go to the top to download the complete standard document for free.
- Recommended standards
- SN/T 1504.2-2005 Plastics used for food container and package -- Part 2: Determination of phenolic antioxidants and erucamide slip additives in linear low-density polyethylene -- Liquid chromatography
- JB/T 7384.16-1994 Fastener rivet hole diameter plug gauge
- GB 18281.1-2000 Biological indicators for sterilization of health care products Part 1: General
- GB 50165-1992 Technical specification for maintenance and reinforcement of wooden structures of ancient buildings
- GB 3752.2-1983 Compression fittings
- GB/T 2900.33-2004 Electrical terminology Power electronics technology
- GB/T 5105-2004 Basic types and dimensions of 45° pressure angle involute spline hobs
- CJJ/T 80-1998 Technical specification for base and subbase of solidified pavement
- CH/T 2005-1999 The electronic data recording rules for triangulation
- JB/T 2001.38-1999 Water system filling valve relay (Type A) (PN=20MPa)
- JB/T 7140.1-1993 Types and basic parameters of livestock medicated bath machines
- JB/T 3355-1998 Centrifugal chiller
- GB 5112-1985 Electron-volt and joule conversion tables
- NY/T 1379-2007 Multi-residue Determination of 334 Pesticides in Vegetable by GC/MS and LC/MS
- GB/T 24570-2009 Aseptic bag forming-filling-sealing machine
Please remember: "bzxz.net" is the combination of the first letters of the Chinese pinyin of the four Chinese characters "standard download" and the international top-level domain name ".net". ©2024 Standard download websitewww.bzxz.net Mail:bzxznet@163.com