Chapter 3 - Short circuit current calc

三相系统中短路电流的计算

Chapter 3 - Short circuit current calc

Calculation of Short-Circuit Currents in Three-Phase Systems

版本年份 1997 文件语言 英语 全文 6 页 格式 PDF
Chapter 3 - Short circuit current calc 三相系统中短路电流的计算封面

标准信息

STANDARD INFORMATION
标准编号
Chapter 3 - Short circuit current calc
所属分类
其他国外标准与工程资料
发布机构
DIN
版本年份
1997
文件语言
英语
文件格式
PDF
文件页数
6 页
文件大小
626.44 KB

中文名称为参考译名,文件语言以原文为准。

· 更新:

标准简介

OVERVIEW

中文简介

该标准规定了三相交流系统中短路电流和短路功率的计算方法。内容涵盖了对称与非对称故障的定义、正序/负序/零序阻抗分析,以及基于DIN VDE 0102/IEC 909标准的初始对称短路电流和峰值短路电流的计算公式。适用于电气网络设备的选型及特性确定,涵盖低压、中压和高压系统。

English summary

This standard specifies the calculation methods for short-circuit currents and powers in three-phase AC systems. It covers definitions of symmetrical and asymmetrical faults, sequence impedance analysis, and formulas for calculating initial symmetrical and peak short-circuit currents based on DIN VDE 0102/IEC 909. It applies to the selection and determination of characteristics for electrical network equipment in low, medium, and high-voltage systems.

以上为根据文件整理的内容简介。

相关标签

标准内容预览

DOCUMENT PREVIEW
点击页码切换内容
Chapter 3 - Short circuit current calcPDF 第 1 页 · 原页码 1

Calculation of peak short-circuit current ip

When calculating the peak short-circuit current ip, sequential faults are disregarded. Three-phase short circuits are treated as though the short circuit occurs in all three conductors simultaneously. We have:

ip = κ · √2 · Ik"

The factor κ takes into account the decay of the d. c. component. It can be calculated as

κ = 1.02 + 0.98 e-3 R/X or taken from Fig. 3-2.

Exact calculation of ip with factor κ is possible only in networks with branches having the same ratios R/X. If a network includes parallel branches with widely different ratios R/X, the following methods of approximation can be applied:

a) Factor κ is determined uniformly for the smallest ratio R/X. One need only consider the branches which are contained in the faulted network and carry partial short-circuit currents.

b) The factor is found for the ratio R/X from the resulting system impedance Zk = Rk + jXk at the fault location, using 1.15 · κk for calculating ip. In low-voltage networks the product 1.15 · κ is limited to 1.8, and in high-voltage networks to 2.0.

c) Factor κ can also be calculated by the method of the equivalent frequency as in IEC 909 para. 9.1.3.2.

The maximum value of κ = 2 is attained only in the theoretical limiting case with an active resistance of R = 0 in the short-circuit path. Experience shows that with a short-circuit at the generator terminals a value of κ = 1.8 is not exceeded with machines < 100 MVA.

With a unit-connected generator and high-power transformer, however, a value of κ = 1.9 can be reached in unfavourable circumstances in the event of a short circuit near the transformer on its high-voltage side, owing to the transformer's very small ratio R/X. The same applies to networks with a high fault power if a short circuit occurs after a reactor.