标准下载网/Chapter 12 - Transformers

Chapter 12 - Transformers

开关柜安装用变压器及其他设备

Chapter 12 - Transformers

Transformers and other Equipment for Switchgear Installations

版本年份 2000 文件语言 英语 全文 6 页 格式 PDF
Chapter 12 - Transformers 开关柜安装用变压器及其他设备封面

标准信息

STANDARD INFORMATION
标准编号
Chapter 12 - Transformers
所属分类
其他国外标准与工程资料
发布机构
ABB
版本年份
2000
文件语言
英语
文件格式
PDF
文件页数
6 页
文件大小
429.57 KB

中文名称为参考译名,文件语言以原文为准。

· 更新:

标准简介

OVERVIEW

中文简介

该文档详细阐述了用于开关柜安装的变压器的设计、类型及尺寸规范。内容涵盖了电力变压器、自耦变压器和升压变压器的分类,干式与油浸式变压器的绝缘介质特性,以及绕组连接组别(向量组)和端子标识方法。此外,还定义了阻抗电压、电压变化及短路电流耐受能力等关键技术参数。

English summary

This document details the design, types, and dimensions of transformers used in switchgear installations. It covers the classification of power, auto, and booster transformers, insulation characteristics of dry-type and oil-immersed units, and winding vector groups with terminal identification. Additionally, it defines key technical parameters such as impedance voltage, voltage variation, and short-circuit current withstand capabilities.

以上为根据文件整理的内容简介。

相关标签

标准内容预览

DOCUMENT PREVIEW
点击页码切换内容
Chapter 12 - TransformersPDF 第 1 页 · 原页码 1

12.1.3 Impedance voltage, voltage variation and short-circuit current withstand

Voltage drops

The impedance voltage UKr is defined as that voltage having the rated frequency which must be applied to the primary side of a transformer so that the rated current Ir flows when the secondary terminals are short-circuited. Since only the short-circuit impedance is present in the circuit,

UKr = √3 · Ir · ZK.

The rated impedance voltage is usually stated as a percentage of the voltage rating Ur of the winding to which the voltage is applied:

uKr = UKr/Ur · 100 %.

The impedance voltage is composed of the ohmic voltage drop (UR, uR) which is in phase with the current, and the reactive voltage (UX, uX), which leads the current in time by 90°.

Ohmic voltage drop:

uRr = PKr/Sr · 100 % = Impedance losses at rated power / rated power · 100 %.

Reactive voltage:

uXr = √(uKr² - uRr²).

In the case of a partial load, the short-circuit voltage UK is proportional to the load on the transformer:

uK = uKr · I/Ir = uKr · S/Sr

For distribution transformers, according to DIN 42500 a rated impedance voltage uKr is allocated to each power rating Sr, Table 12-3.

Table 12-3 Rated impedance voltage uKr
Rated output Sr in kVA1) uKr
50 (63) 100 160 (200) 250 (315) 400 (500) 630 4 %
630 (800) 1000 (1250) 1600 (2000) 2500 6 %

1) Rated outputs not in brackets are preferred.